Compliance with the EU Machinery Directive – Functional SafetyDANGERAny misuse of safety function could lead to personal injury or death, property damage, or economic loss. To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. Cannot assume responsibility for any system to comply with safety directive.ATTENTIONThe information of this manual is merely a guide for proper installation.Mitsubishi Electric Co. Cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this equipment.A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.DANGERTo avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the P(+) and N(-) terminals or test points (refer to your drive’s User Manual for locations and discharging time). The voltage must be zero.DANGERThe safety stop function do not isolate electrically between drive and motor.
To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).ATTENTIONIf you are using a FR-D740-EC or FR-D740-CHT with serial number shown below, safety function does not work according to safety standard. In such case please contact your sales person.D740-012 to 080 –EC: Axxxxx, Bxxxxx, Cxxxxx, Dxxxxx, Exxxx and Fxxxxx D740-120 to 160 –EC: Axxxxx, Bxxxxx, Cxxxxx and DxxxxxD740-0.4K to 3.7K –CHT: Axxxxx, Bxxxxx, Cxxxxx, Dxxxxx,Exxxx and Fxxxxx D740-5.5K to 7.5K –CHT: Axxxxx, Bxxxxx, Cxxxxx and Dxxxxx. General descriptionFeaturesMitsubishi FR-D700 safety stop function prevents a drive from supplying rotational energy to motors.
Dual safety channels ‘S1’ and ‘S2’ cut off the gate-drive power for IGBT to turn off.Input powerFR-D700S2S1IGBTsGateGateSCCPUDriverDriverMFig.1 FR-D700 safety stop function diagramDANGERThe safety stop function doesn’t isolate electrically between drive and motor. To avoid an electric shock hazard, disconnect power to the drive and verify that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).DirectivesMitsubishi FR-D700 safety stop function meets the following directives and categories. EN954-1 Category 3IEC60204-1 Stop category 0DANGERThe misuse of safety function leads to personal injury or death, property damage, or economic loss.To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. Cannot assume responsibility for any system to comply with safety directive.1. Installation and wiringATTENTIONThe following information is merely a guide for proper installation.Mitsubishi Electric Co. Wire and ferrule specificationTable.4 wire and ferrule specificationWire size (mm 2)Ferrule with insulation collar.Crimping tool.0.3 / 0.5AI 0,5-10WH0.75AI 0,75-10GYCRIMPFOX ZA31AI 1-10RD1.25 / 1.5AI1,5-10BK0.75 (combined 2 wire)AI TWIN 2 X 0,75-10GY.Ferrules and tools are distributed by Phoenix Contact.Jumper cableThe jumper cable between S1,S2 and SC terminal has been installed in the factory as shown in Fig.2.AMFig.2.
Short wireBefore connecting safety input wire to S1,S2 and SC terminal, remove this jumper cable.4. Example of safety system configurationExample 1R S TABRYCSTARTSTFSTFSTOPSTOPEMPCSOURCECPUIGBTsGateGateDriverDriver+24VX0COM0 X1COM1XS0XS1Z00Z10Z20SafetyK1S1DC24VLogicCircuitK2S224GZ01Z11Z21SCMITSUBISHI MELSEC Safety relay unitQS90SR2SN-QFR-D700U V WIMFig.3 Safety system example 1 – STOP asynchronous with EM and fault detection through A-C output.For safety stop, configure the wiring as shown in Fig.3 above.Note: the above wiring is configured to prevent restart in case of a fault.The parameter No.192 must be set to ‘199’.
Mitsubishi M-vr 700 Manual 2017
Test and checking failureATTENTIONTo avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check the correct function of the monitor signal.